Sound Testing – Green Man Pub, Harlesden

THE BRIEF

  • We were instructed by a Property Management company to conduct Sound Insulation Testing at a set of flats above The Green Man Pub in Harlesden, London
  • The Sound Insulation Tests consisted of Airborne Floor, Airborne Wall and Impact Floor Tests 
  • To pass these Airborne test, you must score 43db or higher
  • Airborne tests measure the difference in sound levels between the receiver room and neighbouring walls or floors
  • If the sound output in the receiver room is 100db and the sound leakage being passed through into the neighbouring room is 40db, then the result would be 60 and therefore would be a pass
  • To pass these Impact tests, you must score 64db or lower
  • Impact tests measure how effectively the Sound Insulation between floors cancels out sound. If there is less than 62 decibels of sound leaking through into below floors then these tests would be a pass
Sound Testing - Green Man Pub, Harlesden

THE PROCESS

  • After reviewing drawings, on site testing was ready to be completed. All calibrated equipment was setup in accordance to our strict procedures to ensure the most accurate result possible

THE RESULTs

  • SOUND TESTING RESULTS

Airborne Floor Target 

≥ 43

Pub - Flat F Bedroom

≥ 43

Flat F Living Room/Kitchen - Flat K Living Room/Kitchen

≥ 43

Flat I Living Room/Kitchen - Flat J Studio

Impact Floor Target 

≤ 64

Flat J Studio - Flat I Living Room/Kitchen

≤ 64

Flat F Living Room/Kitchen - Flat K Living Room/Kitchen

Airborne Wall Target 

≥ 43

Flat F Living Room/Kitchen - Flat G Living Room/Kitchen

≥ 43

Flat J Studio - Flat K Living Room

Airborne Floor Result

51

Pub - Flat F Bedroom

46

Flat F Living Room/Kitchen - Flat K Living Room/Kitchen

49

Flat I Living Room/Kitchen - Flat J Studio

Impact Floor Result

63

Flat J Studio - Flat I Living Room/Kitchen

59

Flat F Living Room/Kitchen - Flat K Living Room/Kitchen

Airborne Wall Result

52

Flat F Living Room/Kitchen - Flat G Living Room/Kitchen

52

Flat J Studio - Flat K Living Room


PASS


PASS


PASS


PASS


PASS


PASS


PASS

  • Compliant
  • The building's Sound Tests all passed and the Airborne Wall Tests in particular achieved extremely good scores which shows a very good level of Sound Insulation 
  • UK Building Compliance cover Nationwide in the UK; we visited London for these tests 

For further guidance, please see our How To Guides in our Advice Centre here