Sound Testing & Air Testing in Warwick

THE BRIEF

  • To pass an Airborne test for new build properties you must score 45db or higher 
  • Airborne tests measure the difference in sound levels between the receiver room and neighbouring walls or floors
  • If the sound output in the receiver room is 100db and the sound leakage being passed through into the neighbouring room is 40db, then the result would be 60 and therefore would be a pass
Sound Testing & Air Testing in Warwick

THE PROCESS

  • After our technicians calculated the areas of the apartments on site, testing was ready to be carried out. All calibrated equipment was setup in accordance to our strict procedures to ensure the most accurate result possible

THE RESULTs

  • SOUND TESTING RESULTS

Airborne Wall Target

≥ 45

Plot 8 Bedroom - Plot 7 Bedroom

≥ 45

Plot 6 Living/Kitchen - Plot 5 Living/Kitchen

≥ 45

Plot 2 Bedroom - Plot 1 Bedroom

≥ 45

Plot 3 Bedroom - Plot 4 Bedroom

Airborne Wall Result

63

Plot 8 Bedroom - Plot 7 Bedroom

60

Plot 6 Living/Kitchen - Plot 5 Living/Kitchen

47

Plot 2 Bedroom - Plot 1 Bedroom

48

Plot 3 Bedroom - Plot 4 Bedroom

PASS

PASS

PASS

PASS

  • AIR TESTING RESULTS

≤ 5.0 m³.h.m² @ 50pa

Plot 1 - Target

≤ 5.0 m³.h.m² @ 50pa

Plot 3 - Target

≤ 5.0 m³.h.m² @ 50pa

Plot 7 - Target

≤ 5.0 m³.h.m² @ 50pa

Plot 8 - Target

4.82

Plot 1 - Result

4.69

Plot 3 - Result

3.74

Plot 7 - Result

3.26

Plot 8 - Result

PASS

PASS

PASS

PASS

  • Compliant
  • Most of the plots achieved extremely low scores which shows very good levels of Sound Insulation and Air Tightness
  • Our Combined Testing package offers excellent value  

Start Using UK Building Compliance Today


You may also like

January 25, 2024

July 12, 2022

June 27, 2022

June 23, 2022

May 17, 2022

May 12, 2022

Start Using UK Building Compliance Today